DC + AC UPS MODULAR
Example 1
Uin: 3 x 400 / 230 V, 50 Hz
Uout1: 110 VDC, Uout 2: 48 VDC,
Uout 3: 24 VDC,
Uout 4: 230 V, 50 Hz,
Bat: 2 x 110 VDC
STRUCTURE:
– input AC distribution with measurement, protections and distribution,
type: IZBN 1f (3f) – xx
– rectifiers / battery chargers, 1 to 24 pcs in parallel, „n+1“ principle, with fan or natural cooling
type: MPL, MPLP (high power UPS) or PFC, KMB, PBR (UPS low power)
– battery, Lead-Acid or Ni-Cd, 1 or 2 sets
– battery protection (over current, deep discharge, short circuit)
– measuring unit (currents, voltages, temperatures)
type: MJ
– microprocessor unit for local and remote monitoring and control
type: MPJ 02 (03) or MPJ 04
– DC / AC inverters, type: NIZ (high power UPS) or IK (low power UPS)
– automatic Bypass switch, 20 kVA (one phase) or 60 kVA (three phases)
Type: MBP 20k 1f or MBP 60k 3f
– manual Bypass switch
– DC / DC converters (if there needs to be multiple different DC voltage outputs)
type: IDC, ZDC, LLC, SIP
– output AC distribution with protections (MCCB, MCB, fuses), with or without selective disconnection
– output DC distribution with protections (MCCB, MCB, fuses), one or more output voltages, with or without selective disconnection
– cabinet, one or more (rectifiers cabinet + battery cabinet or battery rack + DC/AC and DC /DC cabinet + output distribution cabinet + connecting cabinet)
Functional scheme of the system
Example 2
Uin: 3 x 400 / 230 V, 50 Hz
Uout1: 220 VDC – 44 A
Uout2: 48 VDC – 40 A
Uout3: 230 V, 50 Hz – 7.5 kVA / kW
Bat: 220 V – 155 Ah, VRLA, AGM
Distribution DC: 1, 2 and 3 level of selectivity
Distribution AC: 1 and 2. Level of Selectivity
General technical data
INPUT:
– 230 V, 50 / 60 Hz or
– 3 x 400 / 230 V, 50 / 60 Hz
OUTPUT:
a) AC output
– 230 V, 50 Hz or
– 3 x 400 / 230 V, 50 Hz
b) DC output / outputs
one or more DC output voltages
– 24 VDC,
– 48 VDC,
– 60 VDC,
– 110 VDC,
– 125 VDC,
– 220 VDC,
POWER:
– AC output voltage
100 VA to 20 kVA, one phase output 7,5 kVA to 60 kVA, three phases output
– DC output voltage
100 W to 100 kW
AUTONOMY:
To 100 hours
LEVELS OF DISTRIBUTION SELECTIVITY:
Uin: 3 x 400 / 230 V, 50 Hz,
1 to 4
Example 3
Uin: 3 x 400 / 230 V, 50 Hz,
Uout1: 110 VDC, Uout2: 24
VDC, Uout3: 230 V, 50 Hz,
Uout4: 230 V 50 Hz,
Bat: Ni-Cd 110 V – 2 x 470 Ah
Example 4
Uin: 3 x 400 / 230 V, 50 Hz,
Uout1: 110 VDC – 75 (3×25) A,
Uout2: 24 VDC – 50 (5×10) A
Uout3: 230 V, 50 Hz – 10 (4×2.5) kVA / kW,
Bat: 110 V – 150 Ah, VRLA, AGM
EXPLANATION UPS TYPE:
ISZBN AAA/aaa – BBB/bbb – 1f(or 3f)/ccc – ddd
– AAA/aaa (rectifier voltage / rectifier current)
– BBB/bbb (output voltage DC/DC converters / output current)
– 1f or 3f / ccc (output one phase or three phase / output power kVA
– ddd (battery capacity C10)
For example, ISZBN 220/100 – 48/40 – 1f/7.5k – 200
Values: rectifiers, output 220 VDC – 100 A ,
+ DC/DC converters 220 VDC / 48 VDC – 40 A
+ DC/AC inverters 220 VDC / 230 V,50 Hz
– output power 7.5 kVA
+ battery 220 VDC – C10 = 200 Ah
– the customer needs to define: input voltage, output voltages, output power,
autonomy and specification of output switches