INDUSTRY DC UPS - MODULAR
Example 1
Input: 230 VAC, Output: 24 VDC – 30 A – 150 Ah
STRUCTURE:
– input AC distribution with measurement, protections and distribution,
type: IZBN 1f (3f) – xx
– rectifiers / battery chargers, 1 to 24 pcs in parallel, „n+1“ principle, with fan or natural cooling
type: MPL, MPLP (high power UPS) or PFC, KMB, PBR (low power UPS)
– battery, Lead-acid or Ni-Cd, 1 or 2 sets
– battery protection (over current, deep discharge, short circuit)
– measuring unit (currents, voltages, temperatures)
type: MJ
– microprocessor unit for local and remote monitoring and control
type: MPJ 02, MPJ 03 or MPJ 04
– DC / DC converters (if there needs to be multiple different DC voltage outputs)
type: IDC, ZDC, LLC, SIP
– output DC distribution with protections (MCCB, MCB, fuses), one or more output voltages, with or without selective disconnection
– cabinet, one or more (rectifiers cabinet + battery cabinet + DC/DC cabinet
+ voltage distribution cabinet + DC connecting cabinet)
Example 2
Out: 110 VDC – 60 A
Example 3
Out 1: 220 VDC – 88 A (8 x 11 A)
Out 2: 48 VDC – 20 A (4 x 5 A)
Out 3: 24 VDC – 20 A (2 x 10 A)
GENERAL TECHNICAL DATA
INPUT:
– 230 V, 50 / 60 Hz
– 3 x 400 / 230 V, 50 / 60 Hz
POWER:
100W to 100kW AUTONOMY:
1 to 100 hours, or more
COOLED RECFIFIERS:
With P – natural, without P: fan cooled
OUTPUT:
one or more output voltages
– 24 VDC
– 48 VDC
– 60 VDC
– 110 VDC
– 125 VDC
– 220 VDC
UPS TYPE (order code):
– one output voltage – batteries voltage
IBN xxx – yyy – zzz (xxx – nominal output voltage, yyy – output current, zzz – capacity of battery C10)
For example, IBN 110 – 80 – 200 P (or without P), with P – naturally cooled rectifiers, without P – fan-cooled rectifiers
Values: 110 VDC output voltage, 80 A output current, battery C10 = 200 Ah, natural cooled rectifiers
– two or more output voltages – batteries voltage & DC/DC voltages
For example: IBN 110/120 – 48/50 – 350
Output 1: 110 VDC – 120 A (rectifiers 110 VDC – 120 A)
Output 2: 48 VDC – 50 A (DC / DC converters 110 VDC / 48 VDC – 50 A)
Battery C10 = 350 Ah, the battery is charged with 110 VDC
Fan cooled rectifiers
– the customer needs to define the number, technology and nominal values of the output switches (MCCB, MCB, fuse)
Example 4
Modular uninterruptible power supplies with DC distribution
Input: 3 x 400 / 230 VAC, Output: 220 VDC – 44 A, Battery: VRLA 155 Ah
Example 5
Input: 3 x 400 / 230 V, 50 Hz
Output: 110 VDC – 90 A
Battery: VRLA, 54 cells – 155 Ah